A method is presented for real-time digital control of PWM
(pulsewidth-modulation) inverters for UPS application. Using two state
variables (output voltage and load current) measured at every sampling
time, the DSP (digital signal processor) carries out the real-time
calculation of the inverter pulsewidth for the next sampling time.
Maximum pulsewidth and robustness to the system parameter variation are
obtained by using the next sampling pulsewidth calculation and the PI
compensation, respectively. The control scheme was verified through
simulation and experiment for various cases, including sudden load
change, system parameter variation, and the nonlinear load condition,
and it provides excellent transient response and robustness for various
load conditions